SEW變頻器MOVITRAC-31C系列故障代碼詳表

發布時間:2019-08-02 15:40:26來源:

故障代碼 故障現象/類型 故障原因 解決對策
1 Overcurrent Short circuit/earth fault at the output. Motor too large. Faulty output stage. Remove short-circuit. Connect smaller motor. If fault can still not be reset, contact SEW service.
2 DC link voltage DC link voltage too high. Increase deceleration ramps.
3 Brake chopper Regenerative power too high Braking resistor circuit interrupted Short-circuit in the braking resistor circuit Braking resistance value too high Faulty brake chopper Increase deceleration ramps. Check connecting leads of the braking resistor. Check technical data of the braking resistor. Exchange MOVITRAC® 31C
5 Regenerative overload With active regen. n monit. (P520/P522) and speed control (P770): faulty encoder signals wrong number of pole pairs (P324/P344) value of increments (P773) not correct Check encoder. Check encoder connection. Set number of pole pairs correctly. Set value of increments correctly.
4 Cont. overload ´t utilization too high (> 125(%)). Reduce load.
6 Overtemperature Thermal overload of the inverter. Reduce load and / or ensure adequate cooling.
7 Phase failure With active mains volt. monitor.(P530) Phase missing at TL. X1:1/2/3. Check mains supply.
10 Direction of rotation Only with active speed control (P770): Encoder tracks A/A and B/B are swapped in pairs. Motor rotates in opposite direction. Regen. overload (i.e. with sagging hoist) because of excessive load or BOOST setting too low (P321/P341). Check encoder connection. Exchanging two motor phases. Reduce load or increase BOOST.
11 Speed detection Only with active speed control (P770): Faulty encoder connection. FEN31C/FPI31C option not installed. Check encoder connection. Insert correct option (FEN31C or FPI31C).
12 Mot. overload With active n monit. (P510/P512) and speed control (P770): faulty encoder signals wrong number of pole pairs (P324/P344) value of increments (P773) not correct Check encoder. Check encoder connection. Set number of pole pairs correctly. Set value of increments correctly.
13 Starting conditions With active hoist function (P710/P712): Current too low during the premagnetization phase: Motor rated power selected too small in relation to the inverter rated power. Cross-section of the motor leads too small. Check startup data and carry out new startup if necessary. Check inverter-motor connection. Check cross-section of the motor leads and increase if necessary.
14 Output open With active hoist function (P710/P712): Two or all output phases interrupted. Motor rated power selected too small in relation to the inverter rated power. Check inverter-motor connection. Check startup data and carry out new startup if necessary.
17 Stack overflow Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
18 Stack underflow Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
19 NMI trap Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
20 Undefined opcode Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
21 Protected instr. Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
22 Word op. access Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
23 nstruct. access Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly,
24 Ext. bus access Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.

故障代碼 故障現象/類型 故障原因 解決對策
25 EEPROM Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
26 No connection Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
27 Ext. terminal External fault signal has appeared at a programmable input Eliminate the cause of the fault. Reprogram the terminal, if necessary
28 Fault INTERBUS FFI31C and control mode (P841) = Fieldbus: Faulty monitoring signal. Check Fieldbus connection.
32 Copying Only when copying the parameters (P820): Break or interference in PC or FBG31C connection. Check connection between inverter and PC. Remove FBG31C keypad and plug again.
33 Master-slave Connection master-slave is interrupted. 0V5 connection (RS-485) missing Master or slave defined incorrectly in P880. Check master-slave connection. 0V5-establish connection between master and slave Set P880 correctly.
34 Fieldbus timeout No communication between master and slave within the specified time of the response monitoring. Check communication routine of the master. Increase fieldbus timeout time (P571)/ deactivate monitoring.
35 Connection Encoder-FRS Encoder connection faulty. Power supply of the encoder faulty. Check encoder connection. Check power supply of the encoder.
36 Connection Master-slave Only with FRS and cable break master-slave (P557) = YES: Setpoint connection of slave (TL. 98-101) is disrupted. Master Speed 0 ® slave FRS CTRL is disrupted. Slave FRS CTRL input not assigned. Master Speed 0 output not assigned. No master inverter available. Encoder < 512 pulses per revolution used. Check installation. Check programming of the binary inputs and binary outputs. Check if encoder type is correct.
37 FRS RAM fault Internal fault. If fault occurs repeatedly, contact SEW service.
38 FRS process data fault Fault on interface between inverter and FRS. If fault occurs repeatedly, contact SEW service.
39 FRS parameter data fault Invalid value for FRS parameters (P55_). Check parameter settings.
41 FRS lag fault Polarity of the encoder not set correctly. Acceleration ramps too short. P-gain of the positioning controller too small Speed controller not set property. Value for lag error tolerance too small Change polarity of encoder. Increase ramps. Increase P-gain. Select new parameters for speed controller. Increase lag error tolerance (P551). Check wiring of encoder, motor and mains phases. Check if mechanical system is sluggish or whether drive hit an obstacle.
43 Fault binary output Load on TL. X3:61 > 150 mA. Load on the other binary outputs > 50 mA Short circuit on binary output. Capacitive load on binary output. Check installation of the binary outputs.
、、、、、、、長治變頻器維修、、、、信陽變頻器維修、、、,河南鄭州變頻器專業銷售維修中心,技術精湛,質量可靠,價格比較低,信譽保證!變頻器維修電話:15515598858 0371-56700815
用手機看
SEW變頻器MOVITRAC-31C系列故障代碼詳表

拍下二維碼,信息隨身看

試試用手機掃一掃,
在你手機上繼續觀看此頁面。

主站蜘蛛池模板: 国产福利在线观看永久免费 | 天天艹 | 最近中文国语字幕在线播放视频 | 午夜精品亚洲 | 久久这里只有精品免费播放 | 在线观看亚洲精品国产 | 久久久久久久蜜桃 | 激情视频日本 | 爱操在线视频 | 国产成人精品久久免费动漫 | 特级毛片网站 | 狠狠色丁香婷婷综合久久来 | 亚洲国产精久久久久久久春色 | 三级天堂 | www.亚洲视频.com | 国产原创中文字幕 | 黄页网站 播放器 日本 | 亚洲欧洲一区二区三区在线观看 | 亚洲日本va中文字幕婷婷 | 四虎影院国产精品 | 欧美一级免费看 | 国产精品视频一区麻豆 | 久久精品国产亚洲综合色 | 99久久精品免费看国产情侣 | 99在线播放视频 | 久久综合久色欧美婷婷 | 狠狠久久亚洲欧美专区 | 久热国产视频 | 久久99热这里只有精品 | 男人的网站在线观看 | 涩色在线 | 奇米影视一区二区三区 | 欧美很很干| 中文乱码在线观看 | 亚洲一区欧美 | 国产精品视频久 | 天天夜夜爽 | 九九九精品视频 | 五月婷婷激情网 | 天天爽夜夜爽夜夜爽精品视频 | 欧美亚洲专区 |