SEW變頻器的MOVITRAC-31C系列故障代碼詳表

發布時間:2019-08-02 15:32:39來源:

故障代碼 故障現象/類型 故障原因 解決對策
1 Overcurrent Short circuit/earth fault at the output. Motor too large. Faulty output stage. Remove short-circuit. Connect smaller motor. If fault can still not be reset, contact SEW service.
2 DC link voltage DC link voltage too high. Increase deceleration ramps.
3 Brake chopper Regenerative power too high Braking resistor circuit interrupted Short-circuit in the braking resistor circuit Braking resistance value too high Faulty brake chopper Increase deceleration ramps. Check connecting leads of the braking resistor. Check technical data of the braking resistor. Exchange MOVITRAC® 31C
5 Regenerative overload With active regen. n monit. (P520/P522) and speed control (P770): faulty encoder signals wrong number of pole pairs (P324/P344) value of increments (P773) not correct Check encoder. Check encoder connection. Set number of pole pairs correctly. Set value of increments correctly.
4 Cont. overload ´t utilization too high (> 125(%)). Reduce load.
6 Overtemperature Thermal overload of the inverter. Reduce load and / or ensure adequate cooling.
7 Phase failure With active mains volt. monitor.(P530) Phase missing at TL. X1:1/2/3. Check mains supply.
10 Direction of rotation Only with active speed control (P770): Encoder tracks A/A and B/B are swapped in pairs. Motor rotates in opposite direction. Regen. overload (i.e. with sagging hoist) because of excessive load or BOOST setting too low (P321/P341). Check encoder connection. Exchanging two motor phases. Reduce load or increase BOOST.
11 Speed detection Only with active speed control (P770): Faulty encoder connection. FEN31C/FPI31C option not installed. Check encoder connection. Insert correct option (FEN31C or FPI31C).
12 Mot. overload With active n monit. (P510/P512) and speed control (P770): faulty encoder signals wrong number of pole pairs (P324/P344) value of increments (P773) not correct Check encoder. Check encoder connection. Set number of pole pairs correctly. Set value of increments correctly.
13 Starting conditions With active hoist function (P710/P712): Current too low during the premagnetization phase: Motor rated power selected too small in relation to the inverter rated power. Cross-section of the motor leads too small. Check startup data and carry out new startup if necessary. Check inverter-motor connection. Check cross-section of the motor leads and increase if necessary.
14 Output open With active hoist function (P710/P712): Two or all output phases interrupted. Motor rated power selected too small in relation to the inverter rated power. Check inverter-motor connection. Check startup data and carry out new startup if necessary.
17 Stack overflow Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
18 Stack underflow Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
19 NMI trap Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
20 Undefined opcode Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
21 Protected instr. Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
22 Word op. access Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
23 nstruct. access Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly,
24 Ext. bus access Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
故障代碼 故障現象/類型 故障原因 解決對策
25 EEPROM Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
26 No connection Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
27 Ext. terminal External fault signal has appeared at a programmable input Eliminate the cause of the fault. Reprogram the terminal, if necessary
28 Fault INTERBUS FFI31C and control mode (P841) = Fieldbus: Faulty monitoring signal. Check Fieldbus connection.
32 Copying Only when copying the parameters (P820): Break or interference in PC or FBG31C connection. Check connection between inverter and PC. Remove FBG31C keypad and plug again.
33 Master-slave Connection master-slave is interrupted. 0V5 connection (RS-485) missing Master or slave defined incorrectly in P880. Check master-slave connection. 0V5-establish connection between master and slave Set P880 correctly.
34 Fieldbus timeout No communication between master and slave within the specified time of the response monitoring. Check communication routine of the master. Increase fieldbus timeout time (P571)/ deactivate monitoring.
35 Connection Encoder-FRS Encoder connection faulty. Power supply of the encoder faulty. Check encoder connection. Check power supply of the encoder.
36 Connection Master-slave Only with FRS and cable break master-slave (P557) = YES: Setpoint connection of slave (TL. 98-101) is disrupted. Master Speed 0 ® slave FRS CTRL is disrupted. Slave FRS CTRL input not assigned. Master Speed 0 output not assigned. No master inverter available. Encoder < 512 pulses per revolution used. Check installation. Check programming of the binary inputs and binary outputs. Check if encoder type is correct.
37 FRS RAM fault Internal fault. If fault occurs repeatedly, contact SEW service.
38 FRS process data fault Fault on interface between inverter and FRS. If fault occurs repeatedly, contact SEW service.
39 FRS parameter data fault Invalid value for FRS parameters (P55_). Check parameter settings.
41 FRS lag fault Polarity of the encoder not set correctly. Acceleration ramps too short. P-gain of the positioning controller too small Speed controller not set property. Value for lag error tolerance too small Change polarity of encoder. Increase ramps. Increase P-gain. Select new parameters for speed controller. Increase lag error tolerance (P551). Check wiring of encoder, motor and mains phases. Check if mechanical system is sluggish or whether drive hit an obstacle.
43 Fault binary output Load on TL. X3:61 > 150 mA. Load on the other binary outputs > 50 mA Short circuit on binary output. Capacitive load on binary output. Check installation of the binary outputs.
SEW變頻器的MOVITRAC-31C系列故障代碼詳表鄭州SEW變頻器維修
用手機看
SEW變頻器的MOVITRAC-31C系列故障代碼詳表

拍下二維碼,信息隨身看

試試用手機掃一掃,
在你手機上繼續觀看此頁面。

主站蜘蛛池模板: 国产综合久久久久影院 | 久久久噜噜噜 | 国农村精品国产自线拍 | 午夜成人免费影院 | 国产成人精品无缓存在线播放 | 亚洲成a人片毛片在线 | 欧美一级毛片一级 | 久久精品视频在线 | 国产成人亚洲精品2020 | 亚洲加勒比久久88色综合一区 | 亚洲性综合 | 久久精品国产免费看久久精品 | 女人18毛片a级毛片免费视频 | 欧美黄一片 | 中文字幕 日韩有码 | 国内精品七七久久影院 | 欧洲成人全免费视频网站 | 国产91久久精品一区二区 | 国内自拍一二三四2021 | 国产精品国产色综合色 | 亚洲三级久久 | 网络色综合久久 | 热久久久久久 | 亚洲欧洲国产精品久久 | 亚洲欧美日韩一区 | 乱人伦中文视频在线 | 亚洲欧美香蕉在线日韩精选 | 毛片毛片毛片毛片毛片 | 日韩中文一区 | 免费网站成人亚洲 | 天天骑天天干 | 国产欧美精品区一区二区三区 | 久久伊人成人网 | 午夜毛片福利 | 欧美三级中文字幕 | 91精品国产高清久久久久 | a级毛片免费完整视频 | 美女一级毛片 | 欧美日韩一区二区高清视 | 色综合综合 | 欧美视频在线观看 |